VP 3G F L

Low pressure steam boiler with three flue passes

  • VP 3G F L

Low pressure saturated steam generator, packaged steel structure, with pressurised combustion and high energy efficiency. Ready for operation in combination with a jet burner on liquid or gas fuel. Boiler with three flue passes, combustion chamber with cooled end plate sized to ensure low heating loads.

Range consisting of 10 models with useful heat outputs from 347 kW to 3,467 kW.

 


  • Technical Data

    Standard design pressure 3 bars, assembling design pressure 1 bar or 3 bar

    Steam production from 500 to 5,000 kg/h.

    • The burner anchor door is hinged to the tube plate; it’s insulated on the inside with a suitable layer of refractory concrete which covers the entire heated surface of the plate itself.

    • Amply sized evaporating chamber with large heat exchange area for the production of high quality saturated steam.

    Heat loss to the surrounding environment is limited by a layer of high-density mineral wool on the boiler body, without thermal bridges, protected by stainless steel plate (AISI 430).

    • The parts subject to pressure are all welded by qualified and approved personnel, according to EN standards.

    • These modern-concept and high-efficiency generators have been designed and developed in compliance with European Directive 2014/68/UE (PED) and the most recent national and European standards on pressurised recipients.

    • Certified as an assembly in accordance with the PED Directive.

    • The water circuit can be inspected through a manhole at the top of the boiler and a hand opening ring at the bottom.

    CERTIFICATION

    CE mark in accordance with the following directives

    Pressure Equipment (2014/68/UE)

    Low Voltage (2014/35/UE)

    Electromagnetic Compatibility (2014/30/UE)

    ACCESSORIES AVAILABLE ON REQUEST

    • Economiser: a water-flue gas heat exchanger that increases efficiency by around 4%. Its configuration and position are inside the rear smoke box.

    • Modulating supply system for optimum water level management in combination with an economiser.

    • Burner: brand and type chosen based on customer specifications.

    • Second standby supply pump with valves.

    System for automatically draining sludge and dissolved salts that deposit on the bottom.

    Salinity (TDS) control system that measures dissolved salts in the water.

    Cooling tank for sampling boiler water.

    • BMS 24H for up to 24 hours’ continuous unsupervised operation.

    • BMS 72H for up to 72 hours’ continuous unsupervised operation.

    Second FAIL SAFE minimum level probe.

    FAIL SAFE maximum level probe.

    PLC control system fitted with high performance Touch Panel colour operator interface. The interface can be used to manage operation of the Boiler- Burner-Central Heating System.

    • “VRC” condensate collection vessel.

    • “VRD” atmospheric degasser.

    • “DGST” thermophysical degasser.

    • “BDV” drainage cooling tank.

    • Water treatment system.

    • Steam manifold.

    • Ladder and walkway.

     

Related products

Pic
VAPOPREX LVPq
Low pressure steam boiler with three flue passes, two in furnace
Pic
VAPOPREX LVP
Low pressure steam boiler with three flue passes, two in furnace
Pic
VAPOPREX HVP
Medium pressure steam generator with three flue passes, two in furnace
Pic
VP 3G
Medium pressure steam boiler with three flue passes