TP3 LN
Hot water boiler with three flue passes - LOW NOx
Only for CE markets: Sale and installation of TP3 LN boilers (models from 70 to 4000) only for industrial applications or in accordance with EU Regulation No. 813/2013 (Article 1, Comma 2 , Point G)
Hot water generator with pressurised combustion with three flue gas passes and three-star certified energy efficiency in accordance with directive 92/42/EEC.
Ready for operation in combination with a jet burner on liquid or gas fuel. The arrangement and generous sizing of the combustion chamber guarantee a low heating load and the possibility to be combined with burners featuring technology for the combustion with low polluting emissions.
Range consisting of 20 models with rated outputs from 70 to 3,200 kW.
-
Technical Data
• Boiler body lined on the outside with carbon steel plate protection painted with epoxy powder coat, and consisting of:
pipe for the second flue pass with intake from the bottom of the furnace, sized to optimise combustion parameters;
tube bundle for the third flue gas pass located at the top and hotter part of the hot water generator, so as to prevent condensate forming and fitted with steel
turbulators to increase convective heat exchange.
• Energy efficiency exceeding 95%.
• Design pressure 6 bars.
• Maximum design temperature 100°C.
• Floating combustion chamber with cooled end plate, volumetric heating load less than 1.1 MW/m3 to ensure atmospheric nitrogen oxide emissions less than 80 mg kW/h, in combination with suitable burners.
• Threaded fittings up to 240 kW outputs and flanged fittings complete with counterflanges for larger sizes.
• Front door with reversible opening from both sides and innovative closing system with micrometric adjustment on the boiler body. Heat insulation using with material with excellent insulting properties and
reduced thermal inertia, protected by refractory material on the furnace side and on the flue gas pass side.
• Heat insulation extended to all parts of the boiler using an 80 mm thick layer of mineral wool on all the plating.
CERTIFICATION
CE mark in accordance with the following directives
Gas Appliances (2016/426 GAR)
Low Voltage (2014/35/EU)
Electromagnetic Compatibility (2014/30/EU)
ACCESSORIES AVAILABLE ON REQUEST
• Thermostatic control panel.
Thermostatic controller for single-stage or two-stage burners, with the possibility to control the system pump.
• THETA+ control panel.
Electronic for managing the hot water generator (including with modulating burners), with microprocessor control; logical control unit housed inside the casing and user interface with LCD on the front panel.
• Industrial control panel.
For special needs regarding precision control or installation in safe environments.
• Control panel with PLC.
For specific communication needs to BMS or supervision systems.
• Pipe stub for instrument connection.
Able to house all the boiler control and safety instruments,available in different configurations.
• Gas, oil or diesel burner.
• Perforated burner plate based on customer specifications.
-
Manuals
-
Depliant
-
Certifications