RSW N 2360 - 6000 kW

Hot water boiler with three flue passes, two in furnace

  • RSW N 2360 - 6000 kW

Hot water generator with pressurised combustion, ready for operation in combination with a jet burner on liquid or gas fuel. Completely cooled combustion chamber, sized to ensure low heating loads.
Furnace with flame reversal and low heating load.
Range consisting of 7 models with rated outputs from 2,360 to 6,000 kW.


  • Technical Data

    • Boiler body made entirely from steel, completely lined with an 80 mm layer of high density glass wool, in turn covered by a strong layer of tearproof material.

    Design pressure 6 bars, higher pressures on request.

    • Pressurised combustion chamber, completely cooled and protected by a system ensuring uniform division of the cold system return water, to avoid dangerous temperature differences. The burner is

    not aligned with the combustion chamber but rather has been moved downwards. This assists flame reversal, reduces the flue gas pressure drop and consequently extends the hot water generator’s

    range of application.

    Tube bundle placed above the furnace so as to guarantee the flue gas passes through a hot section of the hot water generator and consequently reduce the possibility of condensate forming.

    Turbulators featuring a new design able to increase heat exchange, without affecting pressure drop in the boiler.

    • Front door with reversible opening (right and left) and innovative closing system with micrometric adjustment on the hot water generator front plate.

    • Flanged PN16 central heating flow outlet and return inlet connections.

    Supplied in two parts, steel body complete with casing, and satellite controls (satellite to be ordered separately).

    CERTIFICATION

    CE mark in accordance with the following directives

    Gas Appliances (2016/426 GAR)

    Low Voltage (2014/35/EU)

    Electromagnetic Compatibility (2014/30/EU)

    ACCESSORIES AVAILABLE ON REQUEST

    Thermostatic control panel.

    Thermostatic controller for single-stage or two-stage

    burners, with the possibility to control the system pump.

    THETA+ control panel.

    Electronic for managing the hot water generator (including with modulating burners), with microprocessor control; logical control unit housed inside the casing and user interface with LCD on the front panel.

    Industrial control panel.

    For special needs regarding precision control or installation in safe environments.

    • Control panel with PLC.

    For specific communication needs to BMS or supervision systems.

    Pipe stub for instrument connection.

    Able to house all the boiler control and safety instruments, available in different configurations.

    • Stainless steel economiser (mod. 3600-6000) to increase system efficiency by up to 5% (based on the system return temperature) by recovering heat from the flue gas.

    Economiser connection complete with return pipe extension, circulating pump with on-off valves and mechanical connection to the economiser performed directly at our facilities.

    • Gas, oil or diesel burner.

    • Perforated burner plate based on customer specifications.

    Ladder and walkway for safe access to the walkable platform on top of the boiler.

     

  • Manuals
  • Depliant
  • Certifications

Related products

Pic
TP3 LN
Hot water boiler with three flue passes - low nox
Pic
PREXTHERM T3G F
Hot water boiler with three flue passes
Pic
PREXTHERM T3G N
Hot water boiler with three flue passes
Pic
RSW N 92 - 1890 kW
Hot water boiler with three flue passes, two in furnace