RCI - RNI
WATER CHILLERS AND AIR/WATER HEAT PUMPS IN CLASS A WITH AXIAL FANS, INVERTER SCROLL COMPRESSOR AND PLATE EXCHANGER
This series of chillers and air-water heat pumps fulfils the requirements for medium-power residential or industrial air conditioning and heating systems.
The entire range is available in R410a or in R454b. The latter is a refrigerant gas with a GWP of 466, over 75% less compared to R410a.
All the units are suitable for outdoor installation and can be used in fan coil, radiant and high-efficiency radiator systems or to extract the heat generated during industrial processes.
The cooling circuit, housed in a separate compartment to make maintenance operations easier, features inverter scroll compressors which ensure greater efficiency to partial loads (SEER/SCOP), all the units are in Class A energy efficiency.
The inverter control on the circulation pump and fans (EC Inverter) are also available as accessories for a greater efficiency. The EC Inverter fans are also available with high pressure head for internal ducted installation.
A wide range of accessories, factory installed or supplied separately, complement the extreme versatility and functionality of the series.
FEATURES
- Free-standing structure made of galvanised sheet metal with added polyester powder coating protection.
- DC INVERTER Scroll compressors internal heat protection and crankcase heater.
- Axial fans coupled directly to the motor with external rotor.
- Finned coil with copper pipes and aluminium fins
- Stainless steel AISI 316 brazed plate exchanger, including water differential pressure switch. The anti-freeze heating element is standard supply in the heat pump unit.
- The cooling circuit has an electronic expansion valve, high and low pressure electronic pressure gauges, and R410A refrigerant. Desuperheater for 20% heat recovery and Total heat recovery unit for 100% recovery are available as options.
- Electrical cabinet with main cut-off switch and door lock device, fuses, thermal relays to protect the compressors and thermal contacts for the fans.
- Condensation check included: proportional electronic device for continuous and efficient operation of the unit with external air temperature as low as -20°C in cooling. The device also guarantees the damping of the sound level especially at night. It consists of a continuous fan rotation speed regulator, high and low pressure transducers in the cooling circuit and electric heater in the electrical cabinet
- Heating operation with external air temperature as low as -15°C.
- The unit is managed by a microprocessor controller to which all loads and control devices are connected via a wiring board. The user interface consists of a four-button display via which it is possible to view and, if necessary, change all the unit operating parameters.
- A remote keypad is available, as an accessory, which replicates all the operations of the interface installed on the machine.
-
Technical Data
AVAILABLE RANGE IN R410A AND R454B:
RCI model, with R410a
RNI model, with R454b, with low environmental impact
xR 050÷180 AB Cooling only
xR 050÷180 AX Super Silenced cooling only
xP 050÷180 AB Reversible heat pump
xP 050÷180 AX Super Silenced reversible heat pump
-
Manuals
-